Available fault current,
at every panel.

Build your system, branch it the way the job really runs, and read the fault current at any point. Free — no login.

Branches like the real jobService → panels → sub-panels, any depth
Edit anything, nothing resetsFat-finger a value? Just fix it.
The NEC 110.24 numbers, ready to readWrite your placard straight off the screen
Free forever for the calculation. TrueFault Pro saves your jobs to re-open and edit later.
Available fault current
18.6kA
at Panel B · 480 V, 3Ø
Result
6 components · 4 points — the whole system on one screen.
To branch: tap a bus to select it, then Add — anything you add downstream of the same bus starts a new branch.
Utility source
Utility service
480 V · 3Ø · 50 kA available
at source
50.0kA
Transformer
T-1 · 1000 kVA
5.75 %Z → 480 V
secondary
22.4kA
Main panel · branches here
MDP — Main
600 A · 480 V · 2 feeders
at bus
21.1kA
RESULT HERE
Feeder A → panel
Panel B
250 ft · 500 kcmil Cu
here
18.6kA
Feeder → sub-panel
Sub-panel B1
60 ft · #4 Cu
here
16.9kA
Motor load
Motor M1 · 50 HP
adds fault current upstream
+2.1 kA
Add downstream of Panel B
Feeder C → panel
Panel C
140 ft · #1/0 Al
here
12.1kA
Tap any item to edit — your other entries never reset.
Available fault current
18.6kA
Add componentdownstream of Panel B
Transformer
Conductor
Motor
Generator
Rating
75
kVA
Primary
480typ
V
Secondary
208typ
V
Impedance %Z
5.75typical
%
Don't know the %Z? 5.75% is typical for this size — leave it and refine from the nameplate later.
Material
Wiring method
Aerial / open-air? Covered — open spacing changes the reactance, so we adjust it automatically (triplex, quadruplex, or open run).
Length
250
ft
Size
500 kcmiltyp
Parallel sets
1typ
×
Motor size
50
HP
Voltage
480typ
V
Contribution auto-figured. A running motor feeds the fault — we add ≈4× its full-load amps where it connects. No FLA handy? We estimate from HP.
Rating
500
kVA
Voltage
480typ
V
Sub-trans Xd″
16typ
%
Xd″ is the generator's subtransient reactance — 16% is a safe typical if it's not on the nameplate.
1
2
3
4
5
6
7
8
9
.
0
Available fault current
18.6kA
at Panel B · 480 V, 3Ø
For your NEC 110.24 field marking
Available fault current18,600 A
Date of calculationJun 29, 2026
Nominal voltage480 V
Phase3-phase
LocationPanel B
Copy to your label maker — or write it straight on the placard.
Coming back to this job? TrueFault Pro saves the whole system to re-open and edit — plus emailed one-line + placard PDF.
See Pro
Launch summer sale — 50% off your first year

Keep your jobs.

The calculation is always free. Pro is for the guy who comes back — save every system and re-edit it any time.

Free, foreverNo login
Fault current at every point
Full branching — any number of panels
NEC 110.24 readout to make your placard
Pro PROsign in to save
Save & re-edit jobs across visits
Emailed placard PDF — cleaner than FC2's
Emailed one-line — with your branching
FIRST YEAR
$39
$19
then $39/yr
$5
per month
The free tier never expires and is never crippled.

Sign in to save

Create your TrueFault account to keep your jobs. Calculating stays free, no account needed.

Continue with Apple
Continue with Google
or
Email
you@company.com
Password
••••••••
Why an account? Saved jobs follow you between your phone and the truck's laptop — a real login does that. The free calculator never asks you to sign in.
Maybe later